# Erzeugt: 11.07.2023 11:53:56                                                                                          #
# --------------------------------------------------------------------------------------------------------------------- #
# User   : MSCHE                                                                                                        #
# Host   : LAPMARSCH01                                                                                                  #
# Pfad   : T:\02_Produktentwicklung\01_PE-Projekte\PE0142 Lima\21 - Zubeh�r\BACnet-Gateway\MBS\Projektierung\11.07.2023 #
# Datei  : 20230711_Projektierung BACnet Modbus Master.xlsm                                                             #
# ===================================================================================================================== #

[M 1 failure]
  name = Kommunikationsstörung zum Regler
  query = pe

[Y 1 holding 1600]
  name = Thermische Desinfektion: Solltemperatur
  query = pe
  format = st
  writecache = yes

[Y 1 holding 1601]
  name = Thermische Desinfektion: Gesamtdauer pro Station
  query = pe
  format = u
  writecache = yes

[Y 1 holding 1602]
  name = Thermische Desinfektion: Einwirkzeit
  query = pe
  format = u
  writecache = yes

[S 1 coil 1603]
  name = Thermische Desinfektion: Starten / abbrechen 
  query = pe
  writecache = yes

[M 1 input 1604]
  name = Thermische Desinfektion: Status
  query = pe
  format = u

[Y 1 holding 1400]
  name = Einzelgerät / Station 1: Temperatur PWH Soll 
  query = pe
  format = st
  writecache = yes

[Y 1 holding 1401]
  name = Einzelgerät / Station 1: Datum Tag 
  query = pe
  format = u
  writecache = yes

[Y 1 holding 1402]
  name = Einzelgerät / Station 1: Datum Monat 
  query = pe
  format = u
  writecache = yes

[Y 1 holding 1403]
  name = Einzelgerät / Station 1: Datum Jahr 
  query = pe
  format = u
  writecache = yes

[Y 1 holding 1404]
  name = Einzelgerät / Station 1: Uhrzeit Stunde 
  query = pe
  format = u
  writecache = yes

[Y 1 holding 1405]
  name = Einzelgerät / Station 1: Uhrzeit Minute 
  query = pe
  format = u
  writecache = yes

[Y 1 holding 1406]
  name = Einzelgerät / Station 1: Uhrzeit Sekunde 
  query = pe
  format = u
  writecache = yes

[X 1 input 1417]
  name = Einzelgerät / Station 1: Firmware-Version 
  query = pe
  format = uh

[X 1 input 1100]
  name = Einzelgerät / Station 1: S1 - HzVL Temperatur 
  query = pe
  format = st

[X 1 input 1101]
  name = Einzelgerät / Station 1: S2 - PWH Temperatur 
  query = pe
  format = st

[X 1 input 1102]
  name = Einzelgerät / Station 1: S3 - PWH-C / PWC Temperatur 
  query = pe
  format = st

[X 1 input 1103]
  name = Einzelgerät / Station 1: S4 - Puffertemperatur unten 
  query = pe
  format = st

[X 1 input 1104]
  name = Einzelgerät / Station 1: S5 - Puffertemperatur mitte 
  query = pe
  format = st

[X 1 input 1106]
  name = Einzelgerät / Station 1: S7 - HzRL Temperatur 
  query = pe
  format = st

[X 1 input 1107]
  name = Einzelgerät / Station 1: S8 - PWH-C Temperatur Zirkulationseintritt 
  query = pe
  format = st

[X 1 input 1108]
  name = Einzelgerät / Station 1: S9 - PWC Temperatur 
  query = pe
  format = st

[X 1 input 1109]
  name = Einzelgerät / Station 1: V - PWH Volumenstrom 
  query = pe
  format = st

[M 1 status 1201]
  name = Einzelgerät / Station 1: R2 - Rücklaufeinschichtung
  query = pe

[M 1 status 1204]
  name = Einzelgerät / Station 1: R5 - Nachladung
  query = pe

[M 1 status 1205]
  name = Einzelgerät / Station 1: R6 - Fehler 
  query = pe

[X 1 input 1206]
  name = Einzelgerät / Station 1: PWM - Ansteuerung der Primärpumpe 
  query = pe
  format = u

[M 1 coil 1300]
  name = Einzelgerät / Station 1: Sammelstörung 
  query = pe

[X 1 input 1301]
  name = Einzelgerät / Station 1: Codierte Fehlermeldungen
  query = pe
  format = u32s

[S 1 holding 1408.1]
  name = Einzelgerät / Station 1: Betriebsart 
  query = pe
  format = sbit06
  writecache = yes

[X 1 holding 1413]
  name = Einzelgerät / Station 1: Kemper Seriennummer  
  query = pe
  format = u32s

[X 1 input 1504]
  name = Einzelgerät / Station 1: Anzahl Schaltspiele R2 - Rücklaufeinschichtung
  query = pe
  format = u32s

[X 1 input 1516]
  name = Einzelgerät / Station 1: Anzahl Schaltspiele R5 - Nachladung
  query = pe
  format = u32s

[X 1 input 1524]
  name = Einzelgerät / Station 1: Betriebsstunden Primärpumpe  
  query = pe
  format = u32s

[M 1 status 1203]
  name = Station 1: R4 - Kaskadenventil
  query = pe

[X 1 input 1512]
  name = Station 1: Anzahl Schaltspiele R4 - Kaskadenventil
  query = pe
  format = u32s

[X 1 input 2100]
  name = Station 2: S1 - HzVL Temperatur 
  query = pe
  format = st

[X 1 input 2101]
  name = Station 2: S2 - PWH Temperatur 
  query = pe
  format = st

[X 1 input 2102]
  name = Station 2: S3 - PWH-C / PWC Temperatur 
  query = pe
  format = st

[M 1 input 2105.1]
  name = Station 2: S6 - Überlaufsensor Spülgruppe 
  query = pe
  format = sbit06

[X 1 input 2109]
  name = Station 2: V - PWH Volumenstrom 
  query = pe
  format = st

[M 1 status 2200]
  name = Station 2: R1 - Spülventil
  query = pe

[M 1 status 2201]
  name = Station 2: R2 - Zirkulationspumpe
  query = pe

[M 1 status 2203]
  name = Station 2: R4 - Kaskadenventil
  query = pe

[X 1 input 2206]
  name = Station 2: PWM - Ansteuerung der Primärpumpe 
  query = pe
  format = u

[M 1 coil 2300]
  name = Station 2: Sammelstörung 
  query = pe

[X 1 input 2301]
  name = Station 2: Codierte Fehlermeldungen
  query = pe
  format = u32s

[S 1 holding 2408.1]
  name = Station 2: Betriebsart 
  query = pe
  format = sbit06
  writecache = yes

[X 1 holding 2413]
  name = Station 2: Kemper Seriennummer  
  query = pe
  format = u32s

[X 1 input 2500]
  name = Station 2: Anzahl Schaltspiele R1 - Spülventil
  query = pe
  format = u32s

[X 1 input 2504]
  name = Station 2: Anzahl Schaltspiele R2 - Zirkulationspumpe
  query = pe
  format = u32s

[X 1 input 2512]
  name = Station 2: Anzahl Schaltspiele R4 - Kaskadenventil
  query = pe
  format = u32s

[X 1 input 2524]
  name = Station 2: Betriebsstunden Primärpumpe  
  query = pe
  format = u32s

[X 1 input 3100]
  name = Station 3: S1 - HzVL Temperatur 
  query = pe
  format = st

[X 1 input 3101]
  name = Station 3: S2 - PWH Temperatur 
  query = pe
  format = st

[X 1 input 3102]
  name = Station 3: S3 - PWH-C / PWC Temperatur 
  query = pe
  format = st

[X 1 input 3109]
  name = Station 3: V - PWH Volumenstrom 
  query = pe
  format = st

[M 1 status 3203]
  name = Station 3: R4 - Kaskadenventil
  query = pe

[X 1 input 3206]
  name = Station 3: PWM - Ansteuerung der Primärpumpe 
  query = pe
  format = u

[M 1 coil 3300]
  name = Station 3: Sammelstörung 
  query = pe

[X 1 input 3301]
  name = Station 3: Codierte Fehlermeldungen
  query = pe
  format = u32s

[S 1 holding 3408.1]
  name = Station 3: Betriebsart 
  query = pe
  format = sbit06
  writecache = yes

[X 1 holding 3413]
  name = Station 3: Kemper Seriennummer  
  query = pe
  format = u32s

[X 1 input 3512]
  name = Station 3: Anzahl Schaltspiele R4 - Kaskadenventil
  query = pe
  format = u32s

[X 1 input 3524]
  name = Station 3: Betriebsstunden Primärpumpe  
  query = pe
  format = u32s

[X 1 input 4100]
  name = Station 4: S1 - HzVL Temperatur 
  query = pe
  format = st

[X 1 input 4101]
  name = Station 4: S2 - PWH Temperatur 
  query = pe
  format = st

[X 1 input 4102]
  name = Station 4: S3 - PWH-C / PWC Temperatur 
  query = pe
  format = st

[X 1 input 4109]
  name = Station 4: V - PWH Volumenstrom 
  query = pe
  format = st

[M 1 status 4203]
  name = Station 4: R4 - Kaskadenventil
  query = pe

[X 1 input 4206]
  name = Station 4: PWM - Ansteuerung der Primärpumpe 
  query = pe
  format = u

[M 1 coil 4300]
  name = Station 4: Sammelstörung 
  query = pe

[X 1 input 4301]
  name = Station 4: Codierte Fehlermeldungen
  query = pe
  format = u32s

[S 1 holding 4408.1]
  name = Station 4: Betriebsart 
  query = pe
  format = sbit06
  writecache = yes

[X 1 holding 4413]
  name = Station 4: Kemper Seriennummer  
  query = pe
  format = u32s

[X 1 input 4512]
  name = Station 4: Anzahl Schaltspiele R4 - Kaskadenventil
  query = pe
  format = u32s

[X 1 input 4524]
  name = Station 4: Betriebsstunden Primärpumpe  
  query = pe
  format = u32s

[X 1 input 5100]
  name = Station 5: S1 - HzVL Temperatur 
  query = pe
  format = st

[X 1 input 5101]
  name = Station 5: S2 - PWH Temperatur 
  query = pe
  format = st

[X 1 input 5102]
  name = Station 5: S3 - PWH-C / PWC Temperatur 
  query = pe
  format = st

[X 1 input 5109]
  name = Station 5: V - PWH Volumenstrom 
  query = pe
  format = st

[M 1 status 5203]
  name = Station 5: R4 - Kaskadenventil
  query = pe

[X 1 input 5206]
  name = Station 5: PWM - Ansteuerung der Primärpumpe 
  query = pe
  format = u

[M 1 coil 5300]
  name = Station 5: Sammelstörung 
  query = pe

[X 1 input 5301]
  name = Station 5: Codierte Fehlermeldungen
  query = pe
  format = u32s

[S 1 holding 5408.1]
  name = Station 5: Betriebsart 
  query = pe
  format = sbit06
  writecache = yes

[X 1 holding 5413]
  name = Station 5: Kemper Seriennummer  
  query = pe
  format = u32s

[X 1 input 5512]
  name = Station 5: Anzahl Schaltspiele R4 - Kaskadenventil
  query = pe
  format = u32s

[X 1 input 5524]
  name = Station 5: Betriebsstunden Primärpumpe  
  query = pe
  format = u32s